Company Profile Services News Letter Inventory Catalog Listing  
Home Contact Us Staff Login  
  Communication, Signal
& Coaxial Cables
  Data & Low
Capacitance Cables
  Fire Alarm Cables
  Instrumentation &
Tray Cable
  Thermocouple Wire
  Hook-Up Wire
  Custom Designed
Cable Worksheet
  Track Your Order
 
Search
  Aerospace Part No:
 
  Enter a complete or
partial Aerospace P/N.
  Competitor's Part No:
 
  Enter a Belden, Alpha, Berk-Tek or West Penn P/N.
 
 
  Plenum: [ Multi-Conductors (UL) CL2P/CMP Unshielded: 24 & 22 AWG ] (Color Code Chart)
Stranded. (UL) CL2P or CMP. 200°C, 150°C and 60°C.
  Note: Photo is for reference only.  Actual color, conductors, etc. depend on part number.
 
AWG 24 (7x32) Tinned Copper
Aero P/N # of Cond. Insulation Thickness (inches) Jacket Thickness (inches) Jacket O.D. (inches) Lbs / 1000'
1291 2 .006 .010 .092 6
1391 3 .006 .010 .097 8
1491 4 .006 .010 .107 10
1591 5 .006 .010 .117 13
1691 6 .006 .010 .128 15
1791 7 .006 .010 .128 17
1891 8 .006 .010 .164 20
1991 9 .006 .010 .164 22
1091 10 .006 .010 .164 24
1191 12 .006 .010 .169 28
1191-15 15 .006 .010 .189 34
1191-16 16 .006 .010 .189 36
1191-20 20 .006 .010 .211 44
1191-25 25 .006 .010 .236 54
1191-26 26 .006 .010 .236 56
           
AWG 22 (7x30) Tinned Copper
Aero P/N # of Cond. Insulation Thickness (inches) Jacket Thickness (inches) Jacket O.D. (inches) Lbs / 1000'
1281 2 .006 .010 .104 8
1281R 2 .006 .010 .104 8
1381 3 .006 .010 .110 11
1481 4 .006 .010 .121 14
1481R 4 .006 .010 .121 14
1581 5 .006 .010 .133 18
1681 6 .006 .010 .146 21
1781 7 .006 .010 .146 23
1881 8 .006 .010 .188 27
1981 9 .006 .010 .188 30
1081 10 .006 .010 .188 33
1181 12 .006 .010 .194 39
1181-15 15 .006 .010 .217 48
1181-25 25 .006 .012 .276 77
           
 
Specifications

Conductor:
Stranded T.C.

Insulation:
FEP

Color Code:
Chart 1

Jackets Available:
FEP (200°C) or
Fluorocopolymer (150°C) Add "K"
Aeroflex (75°C) Add "PV" to P/N

Industry Approvals:
NEC Article 725-CL2P or
NEC Article 800-CMP
C(UL) (CMP only)

Impedance: (FEP only)
(AWG 24) 100 Ohms Nom.
(AWG 22) 90 Ohms Nom.

Vel. of Propagation: (FEP only)
69% Nom.

Capacitance: (FEP only)
(AWG 24) 15 pF/ft Nom.
(AWG 22) 17 pF/ft Nom.

Operating Temperature Range:
-80°C to +200°C (FEP/FEP)
-40°C to +150°C (FEP/E-CTFE)
-5°C to +75°C (Halar/Aeroflex)

Put Ups:
1000 Feet (+/- 10%)
(Available in Bulk Reels)

Add to P/N:
*HPV = for Halar/Aeroflex
*R = for Red Jacket CMP/200°C